The Airolite Company,LLC: Architectural Louvers, Grilles and Sun Controls
logobottom Home Contact RepNet
Products > Louvers > Fabricated Stationary
 

Airolite’s Fabricated Stationary louvers are designed for applications that require intake and exhaust ventilation with moderate protection against water penetration. Fabricated Stationary louvers are available in 20, 18 and 16 gauge material thickness and 4 and 6-inch frame depths.

601C/FCB601C is a sightproof louver suitable for louver installations at grade or wherever security and resistance to intrusion are primary concern. The inverted V-blade is 100% sightproof when viewed from any orientation and provides additional strength and rigidity for applications subject to sever physical abuse.

601C Material:
Galvanized Steel
Louver Depth:
4” (101.6 mm)
Blade:
16 gauge (1.52 mm)
Frame:
16 gauge (1.52 mm)
Blade Angle:
60º
Free Area - 4 ft. x 4 ft. unit:
4.91 ft² (0.46 m²)
Percent Free Area:
33%
Beginning Point of Water Penetration:
695 fpm (3.53 m/s)
Air Volume Flow Rate at
    Beginning Point of Water Penetration:
3,412 cfm (1.14 m³/s)
Pressure Drop at
    Beginning Point of Water Penetration:
0.25 in. H2O (0.063 kPa)

Product Submittal (PDF); Specification Document (PDF); AutoCAD Drawing (PDF) (DWG)


609/FCB609 is an architectural louver designed for applications that require intake and exhaust ventilation with moderate protection against water penetration. Galvanized steel louvers are more resilient than extruded aluminum louvers when security is a concern or installed at grade or subject to physical abuse.

609 Material:
Galvanized Steel
Louver Depth:
4” (101.6 mm)
Blade:
20 gauge (1.01 mm)
Frame:
16 gauge (1.52 mm)
Blade Angle:
43º
Test Standard:
AMCA Standard 500-L
Free Area - 4 ft. x 4 ft. unit:
7.55 ft² (0.70 m²)
Percent Free Area:
47%
Beginning Point of Water Penetration:
839 fpm (4.25 m/s)
Air Volume Flow Rate at
    Beginning Point of Water Penetration:
6,334 cfm (2.98 m³/s)
Pressure Drop at
    Beginning Point of Water Penetration:
0.09 in. H2O (0.023 kPa)

Product Submittal (PDF); Specification Document (PDF); AutoCAD Drawing (PDF) (DWG)


6096/FCB6096 is an architectural louver designed for applications that require intake and exhaust ventilation with moderate protection against water penetration. Galvanized steel louvers are more resilient than extruded aluminum louvers when security is a concern or installed at grade or subject to physical abuse.

6096 Material:
Galvanized Steel
Louver Depth:
6” (152.4 mm)
Blade:
20 gauge (1.01 mm)
Frame:
16 gauge (1.52 mm)
Blade Angle:
43º
Test Standard:
AMCA Standard 500-L
Free Area - 4 ft. x 4 ft. unit:
7.57 ft² (0.70 m²)
Percent Free Area:
47%
Beginning Point of Water Penetration:
896 fpm (4.55 m/s)
Air Volume Flow Rate at
    Beginning Point of Water Penetration:
6,783 cfm (3.20 m³/s)
Pressure Drop at
    Beginning Point of Water Penetration:
0.15 in. H2O (0.038 kPa)

Product Submittal (PDF); Specification Document (PDF); AutoCAD Drawing (PDF) (DWG)


6774/FCB6774 is a drainable louver de singed to achieve high volume air flow and provide superior resistance to water penetration. Drainable louvers are characterized by gutters incorporated at the front edge of each blade to prevent water droplets from cascading from blade-to-blade and becoming entrained in the intake air flow.

6774 Material:
Galvanized Steel
Louver Depth:
4” (101.6 mm)
Blade:
20 gauge (1.01 mm)
Frame:
16 gauge (1.52 mm)
Blade Angle:
43º
Test Standard:
AMCA Standard 500-L
Free Area - 4 ft. x 4 ft. unit:
7.03 ft² (0.65 m²)
Percent Free Area:
44%
Beginning Point of Water Penetration:
1,250 fpm (6.35 m/s)
Air Volume Flow Rate at
    Beginning Point of Water Penetration:
8,788 cfm (4.14 m³/s)
Pressure Drop at
    Beginning Point of Water Penetration:
0.24 in. H2O (0.060 kPa)

Product Submittal (PDF); Specification Document (PDF); AutoCAD Drawing (PDF) (DWG)


6776/FCB6776 is a drainable louver de singed to achieve high volume air flow and provide superior resistance to water penetration. Drainable louvers are characterized by gutters incorporated at the front edge of each blade to prevent water droplets from cascading from blade-to-blade and becoming entrained in the intake air flow.

6776 Material:
Galvanized Steel
Louver Depth:
6” (152.4 mm)
Blade:
20 gauge (1.01 mm)
Frame:
16 gauge (1.52 mm)
Blade Angle:
43º
Test Standard:
AMCA Standard 500-L
Free Area - 4 ft. x 4 ft. unit:
8.15 ft² (0.76 m²)
Percent Free Area:
51%
Beginning Point of Water Penetration:
948 fpm (4.81 m/s)
Air Volume Flow Rate at
    Beginning Point of Water Penetration:
7,726 cfm (3.65 m³/s)
Pressure Drop at
    Beginning Point of Water Penetration:
0.18 in. H2O (0.045 kPa)

Product Submittal (PDF); Specification Document (PDF); AutoCAD Drawing (PDF) (DWG)


Downloadable Airolite Literature:
All Products Brochure (Sweets)
Corporate Brochure

Get Adobe Reader
You will need the free Acrobat Reader to view and print PDF documents. Click here to download a copy.