Airolite’s Fabricated Stationary louvers are designed for applications that require intake and exhaust ventilation with moderate protection against water penetration. Fabricated Stationary louvers are available in 20, 18 and 16 gauge material thickness and 4 and 6-inch frame depths.
Note: If you're having problems opening these DWG files, you can save the file to your computer desktop.
In Internet Explorer: Right-click on the file and select "Save Target As…"
In Firefox: Right-click and select "Save Link As…"
601C/FCB601C is a sightproof louver suitable for louver installations at grade or wherever security and resistance to intrusion are primary concern. The inverted V-blade is 100% sightproof when viewed from any orientation and provides additional strength and rigidity for applications subject to sever physical abuse.
 |
Material: |
Galvanized Steel
|
| Louver Depth: |
4” (101.6 mm)
|
| Blade: |
16 gauge (1.52 mm)
|
| Frame: |
16 gauge (1.52 mm)
|
| Blade Angle: |
60º
|
| Free Area - 4 ft. x 4 ft. unit: |
4.91 ft² (0.46 m²)
|
| Percent Free Area: |
33%
|
| Beginning Point of Water Penetration: |
695 fpm (3.53 m/s)
|
Air Volume Flow Rate at
Beginning Point of Water Penetration: |
3,412 cfm (1.14 m³/s)
|
Pressure Drop at
Beginning Point of Water Penetration: |
0.25 in. H2O (0.063 kPa)
|
Product Submittal (PDF); Specification Document (PDF); AutoCAD Drawing (PDF)
(DWG)
609/FCB609 is an architectural louver designed for applications that require intake and exhaust ventilation with moderate protection against water penetration. Galvanized steel louvers are more resilient than extruded aluminum louvers when security is a concern or installed at grade or subject to physical abuse.
 |
Material: |
Galvanized Steel
|
| Louver Depth: |
4” (101.6 mm)
|
| Blade: |
20 gauge (1.01 mm)
|
| Frame: |
16 gauge (1.52 mm)
|
| Blade Angle: |
43º
|
| Test Standard: |
AMCA Standard 500-L
|
| Free Area - 4 ft. x 4 ft. unit: |
7.55 ft² (0.70 m²)
|
| Percent Free Area: |
47% |
| Beginning Point of Water Penetration: |
839 fpm (4.25 m/s)
|
Air Volume Flow Rate at
Beginning Point of Water Penetration: |
6,334 cfm (2.98 m³/s)
|
Pressure Drop at
Beginning Point of Water Penetration: |
0.09 in. H2O (0.023 kPa) |
Product Submittal (PDF); Specification Document (PDF); AutoCAD Drawing (PDF)
(DWG)
6096/FCB6096 is an architectural louver designed for applications that require intake and exhaust ventilation with moderate protection against water penetration. Galvanized steel louvers are more resilient than extruded aluminum louvers when security is a concern or installed at grade or subject to physical abuse.
 |
Material: |
Galvanized Steel
|
| Louver Depth: |
6” (152.4 mm)
|
| Blade: |
20 gauge (1.01 mm)
|
| Frame: |
16 gauge (1.52 mm)
|
| Blade Angle: |
43º
|
| Test Standard: |
AMCA Standard 500-L
|
| Free Area - 4 ft. x 4 ft. unit: |
7.57 ft² (0.70 m²)
|
| Percent Free Area: |
47% |
| Beginning Point of Water Penetration: |
896 fpm (4.55 m/s)
|
Air Volume Flow Rate at
Beginning Point of Water Penetration: |
6,783 cfm (3.20 m³/s)
|
Pressure Drop at
Beginning Point of Water Penetration: |
0.15 in. H2O (0.038 kPa)
|
Product Submittal (PDF); Specification Document (PDF); AutoCAD Drawing (PDF)
(DWG)
6096HP/FCB6096HP is a drainable louver designed to provide high volume air flow and resistance to water penetration. The louver incorporates a drainable head-frame to prevent water from cascading from shear-watts onto the louver assembly and becoming entrained in the intake air flow.
 |
Material: |
Galvanized Steel
|
| Louver Depth: |
6” (152.4 mm) |
| Blade: |
16 gauge (1.52 mm)
|
| Frame: |
16 gauge (1.52 mm)
|
| Blade Angle: |
45º
|
| Test Standard: |
AMCA Standard 500-L
|
| Free Area - 4 ft. x 4 ft. unit: |
8.18 ft² (0.76 m²)
|
| Percent Free Area: |
51% |
| Beginning Point of Water Penetration: |
979 fpm (4.97 m/s)
|
Air Volume Flow Rate at
Beginning Point of Water Penetration: |
8,088 cfm (3.78 m³/s)
|
Pressure Drop at
Beginning Point of Water Penetration: |
0.14 in. H2O (0.035 kPa)
|
Product Submittal (PDF); Specification Document (PDF); AutoCAD Drawing (PDF)
(DWG)
6774/FCB6774 is a drainable louver de singed to achieve high volume air flow and provide superior resistance to water penetration. Drainable louvers are characterized by gutters incorporated at the front edge of each blade to prevent water droplets from cascading from blade-to-blade and becoming entrained in the intake air flow.
 |
Material: |
Galvanized Steel
|
| Louver Depth: |
4” (101.6 mm)
|
| Blade: |
20 gauge (1.01 mm)
|
| Frame: |
16 gauge (1.52 mm)
|
| Blade Angle: |
43º
|
| Test Standard: |
AMCA Standard 500-L
|
| Free Area - 4 ft. x 4 ft. unit: |
7.03 ft² (0.65 m²)
|
| Percent Free Area: |
44% |
| Beginning Point of Water Penetration: |
1,250 fpm (6.35 m/s)
|
Air Volume Flow Rate at
Beginning Point of Water Penetration: |
8,788 cfm (4.14 m³/s)
|
Pressure Drop at
Beginning Point of Water Penetration: |
0.24 in. H2O (0.060 kPa)
|
Product Submittal (PDF); Specification Document (PDF); AutoCAD Drawing (PDF)
(DWG)
6766/FCB6766 is a deep dual drainable louver designed to achieve high volume air flow and provide superior resistance to water penetration. Dual drainable louvers are characterized by two gutters incorporate in each blade to prevent water droplets from cascading from blade-to-blade and becoming entrained in the intake air flow.
 |
Material: |
Galvanized Steel
|
| Louver Depth: |
6” (152.4 mm)
|
| Blade: |
16 gauge (1.52 mm)
|
| Frame: |
16 gauge (1.52 mm)
|
| Test Standard: |
AMCA Standard 500-L
|
| Free Area - 4 ft. x 4 ft. unit: |
7.45 ft² (0.68 m²)
|
| Percent Free Area: |
47% |
| Beginning Point of Water Penetration: |
1,127 fpm (5.72 m/s)
|
Air Volume Flow Rate at
Beginning Point of Water Penetration: |
8,396 cfm (3.89 m³/s)
|
Pressure Drop at
Beginning Point of Water Penetration: |
0.15 in. H2O (0.04 kPa)
|
Product Submittal (PDF); Specification Document (PDF); AutoCAD Drawing (PDF)
(DWG)
6776/FCB6776 is a drainable louver de singed to achieve high volume air flow and provide superior resistance to water penetration. Drainable louvers are characterized by gutters incorporated at the front edge of each blade to prevent water droplets from cascading from blade-to-blade and becoming entrained in the intake air flow.
 |
Material: |
Galvanized Steel
|
| Louver Depth: |
6” (152.4 mm)
|
| Blade: |
20 gauge (1.01 mm)
|
| Frame: |
16 gauge (1.52 mm)
|
| Blade Angle: |
43º
|
| Test Standard: |
AMCA Standard 500-L
|
| Free Area - 4 ft. x 4 ft. unit: |
8.15 ft² (0.76 m²)
|
| Percent Free Area: |
51% |
| Beginning Point of Water Penetration: |
948 fpm (4.81 m/s)
|
Air Volume Flow Rate at
Beginning Point of Water Penetration: |
7,726 cfm (3.65 m³/s)
|
Pressure Drop at
Beginning Point of Water Penetration: |
0.18 in. H2O (0.045 kPa)
|
Product Submittal (PDF); Specification Document (PDF); AutoCAD Drawing (PDF)