Airolite Storm ClassTM
louvers are designed and rated to provide high volume intake and exhaust ventilation and prevent water penetration under the most severe wind-driven rain conditions. Storm Class louvers are available with either horizontal or vertical blades and range in frame depths from 2 to 8-inches.
SCC725 is a Storm Class combination louver designed and rated
to provide high volume intake and exhaust ventilation and the greatest level
of protection against water penetration. The design incorporates exterior and
interior louver modules that afford the designer optimum flexibility in aesthetic,
economic and performance considerations.
 |
Material: |
Extruded
Aluminum, Alloy 6063-T5 |
| Louver Depth: |
7
1/4” (184.2 mm) |
| Blade: |
0.081”
(2.06 mm) |
| Frame: |
0.081”
(2.06 mm) |
| Test Standard: |
AMCA
Standard 500-L |
| Water Penetration Test: |
Wind-Driven
Rain |
| Free Area - 4 ft. x 4 ft.
unit: |
5.05
ft² (0.469 m²) |
| Percent Free Area: |
32% |
| Beginning Point of Water Penetration: |
1,250
fpm (6.35 m/s) |
Air Volume Flow Rate at
Beginning Point of Water Penetration: |
7,312
cfm (3.45 m3/s) |
Pressure Drop at
Beginning Point of Water Penetration: |
0.40
in. H2O (0.100 kPa) |
| Wind-Driven Rain Water Penetration
Test: |
|
| Exterior
Wind Velocity: |
29
mph (13 m/s) |
| Rainfall
Rate: |
3”
(75 mm)/hr |
| Effectiveness: |
100.0% |
| Core Ventilation: |
689
fpm (3.5 m/s) |
| Exterior
Wind Velocity: |
50
mph (22 m/s) |
| Rainfall
Rate: |
8”
(200 mm)/hr |
| Effectiveness: |
100.0% |
| Core Ventilation: |
689
fpm (3.5 m/s) |
Product Submittal (PDF);
Specification Document (PDF);
AutoCAD Drawing (PDF)
(DWG)
SCC735 is a Storm Class combination louver designed and rated
to provide high volume intake and exhaust ventilation and the greatest level
of protection against water penetration. The design incorporates exterior and
interior louver modules that afford the designer optimum flexibility in aesthetic,
economic and performance considerations.
 |
Material: |
Extruded
Aluminum, Alloy 6063-T5
|
| Louver Depth: |
7
3/8” (187.3 mm)
|
| Front Blade: |
0.081”
(2.06 mm)
|
| Back Blade: |
0.081”
(2.06 mm)
|
| Frame: |
0.081”
(2.06 mm)
|
| Test Standard: |
AMCA
Standard 500-L
|
| Water Penetration Test: |
Wind-Driven
Rain
|
| Free Area - 4 ft. x 4 ft.
unit: |
8.73
ft² (0.546 m²)
|
| Percent Free Area: |
55%
|
| Beginning Point of Water Penetration: |
1,250
fpm (6.35 m/s)
|
Air Volume Flow Rate at
Beginning Point of Water Penetration: |
7,225
cfm (3.47 m³/s)
|
Pressure Drop at
Beginning Point of Water Penetration: |
0.30
in. H2O (0.075 kPa)
|
| Wind-Driven Rain Water Penetration
Test: |
|
| Exterior
Wind Velocity: |
29
mph (13 m/s)
|
| Rainfall
Rate: |
3”
(75 mm)/hr
|
| Effectiveness: |
100.0%
|
| Core Ventilation: |
689
fpm (3.5 m/s)
|
Product Submittal (PDF);
Specification Document (PDF);
AutoCAD Drawing (PDF)
(DWG)
SCC875 is a Storm Class combination louver designed and rated
to provide high volume intake and exhaust ventilation and the greatest level
of protection against water penetration. The design incorporates exterior and
interior louver modules that afford the designer optimum flexibility in aesthetic,
economic and performance considerations.
 |
Material: |
Extruded
Aluminum, Alloy 6063-T5
|
| Louver Depth: |
8
3/4” (222.3 mm)
|
| Front Blade: |
0.081”
(2.06 mm)
|
| Back Blade: |
0.081”
(2.06 mm)
|
| Frame: |
0.081”
(2.06 mm)
|
| Test Standard: |
AMCA
Standard 500-L
|
| Water Penetration Test: |
Wind-Driven
Rain
|
| Free Area - 4 ft. x 4 ft.
unit: |
8.62
ft² (0.987 m²)
|
| Percent Free Area: |
54%
|
| Beginning Point of Water Penetration: |
1,250
fpm (6.35 m/s)
|
Air Volume Flow Rate at
Beginning Point of Water Penetration: |
10,775
cfm (5.09 m³/s)
|
Pressure Drop at
Beginning Point of Water Penetration: |
0.30
in. H2O (0.075 kPa)
|
| Wind-Driven Rain Water Penetration
Test: |
|
| Exterior
Wind Velocity: |
29
mph (13 m/s)
|
| Rainfall
Rate: |
3”
(75 mm)/hr
|
| Effectiveness: |
100.0%
|
| Core Ventilation: |
689
fpm (3.5 m/s)
|
Product Submittal (PDF);
Specification Document (PDF);
AutoCAD Drawing (PDF)
(DWG)
SCH201 is a Storm Class louver designed and rated to provide
high volume intake and exhaust ventilation and the greatest level of protection
against water penetration. The design incorporates a drainable head member and
horizontal blades to provide maximum resistance to wind-driven rain.
 |
Material: |
Extruded
Aluminum, Alloy 6063-T5
|
| Louver Depth: |
2”
(50.8 mm)
|
| Blade: |
0.063”
(1.60 mm)
|
| Frame: |
0.063”
(1.60 mm)
|
| Test Standard: |
AMCA
Standard 500-L
|
| Water Penetration Test: |
Wind-Driven
Rain
|
| Free Area - 4 ft. x 4 ft.
unit: |
6.20
ft² (0.576 m²)
|
| Percent Free Area: |
39%
|
| Beginning Point of Water Penetration: |
914
fpm (4.64 m/s)
|
Air Volume Flow Rate at
Beginning Point of Water Penetration: |
5,667
cfm (2.67 m³/s)
|
Pressure Drop at
Beginning Point of Water Penetration: |
0.198
in. H2O (0.049 kPa)
|
| Wind-Driven Rain Water Penetration
Test: |
|
| Exterior
Wind Velocity: |
29
mph (13 m/s)
|
| Rainfall
Rate: |
3”
(75 mm)/hr
|
| Effectiveness: |
99.9%
|
| Core Ventilation: |
178
fpm (0.9 m/s)
|
| Exterior
Wind Velocity: |
50
mph (22 m/s)
|
| Rainfall
Rate: |
8”
(200 mm)/hr
|
| Effectiveness: |
99.5%
|
| Core Ventilation: |
99
fpm (0.5 m/s)
|
Product Submittal (PDF);
Specification Document (PDF);
AutoCAD Drawing (PDF)
(DWG)
SCH401 is a Storm Class louver designed and rated to provide
high volume intake and exhaust ventilation and the greatest level of protection
against water penetration. The design incorporates a drainable head member and
horizontal blades to provide maximum resistance to wind-driven rain.
 |
Material: |
Extruded
Aluminum, Alloy 6063-T5 |
| Louver Depth: |
4”
(101.6 mm) |
| Blade: |
0.081”
(2.06 mm) |
| Frame: |
0.081”
(2.06 mm) |
| Test Standard: |
AMCA
Standard 500-L |
| Water Penetration Test: |
Wind-Driven
Rain |
| Free Area - 4 ft. x 4 ft.
unit: |
6.72
ft² (0.625 m²) |
| Percent Free Area: |
42% |
| Beginning Point of Water Penetration: |
1,250
fpm (6.35 m/s) |
Air Volume Flow Rate at
Beginning Point of Water Penetration: |
8,400
cfm (3.96 m³/s) |
Pressure Drop at
Beginning Point of Water Penetration: |
0.296
in. H2O (0.07 kPa) |
| Wind-Driven Rain Water Penetration
Test: |
|
| Exterior
Wind Velocity: |
29
mph (13 m/s) |
| Rainfall
Rate: |
3”
(75 mm)/hr |
| Effectiveness: |
100.0% |
| Core Ventilation: |
295
fpm (1.5 m/s) |
| Exterior
Wind Velocity: |
50
mph (22 m/s) |
| Rainfall
Rate: |
8”
(200 mm)/hr |
| Effectiveness: |
99.1% |
| Core Ventilation: |
98
fpm (0.5 m/s) |
Product Submittal (PDF);
Specification Document (PDF);
AutoCAD Drawing (PDF)
(DWG)
SCH501 is a Storm Class louver designed and rated to provide
high volume intake and exhaust ventilation and the greatest level of protection
against water penetration. The design incorporates a drainable head member and
horizontal blades to provide maximum resistance to wind-driven rain.
 |
Material: |
Extruded
Aluminum, Alloy 6063-T5
|
| Louver Depth: |
5”
(127.0 mm)
|
| Blade: |
0.081”
(2.06 mm)
|
| Frame: |
0.081”
(2.06 mm)
|
| Test Standard: |
AMCA
Standard 500-L
|
| Water Penetration Test: |
Wind-Driven
Rain
|
| Free Area - 4 ft. x 4 ft.
unit: |
6.80
ft² (0.632 m²)
|
| Percent Free Area: |
43%
|
| Beginning Point of Water Penetration: |
1,250
fpm (6.35 m/s)
|
Air Volume Flow Rate at
Beginning Point of Water Penetration: |
9,337
cfm (4.41 m³/s)
|
Pressure Drop at
Beginning Point of Water Penetration: |
0.18
in. H2O (0.045 kPa)
|
| Wind-Driven Rain Water Penetration
Test: |
|
| Exterior
Wind Velocity: |
29
mph (13 m/s)
|
| Rainfall
Rate: |
3”
(75 mm)/hr
|
| Effectiveness: |
99.1%
|
| Core Ventilation: |
300
fpm (1.5 m/s)
|
| Exterior
Wind Velocity: |
50
mph (22 m/s)
|
| Rainfall
Rate: |
8”
(200 mm)/hr
|
| Effectiveness: |
97.2%
|
| Core Ventilation: |
700
fpm (3.5 m/s)
|
Product Submittal (PDF);
Specification Document (PDF);
AutoCAD Drawing (PDF)
(DWG)
SCH601 is a Storm Class louver designed and rated to provide high volume intake and exhaust ventilation and the greatest level of protection against water penetration. The design incorporates a drainable head member and horizontal blades to provide maximum resistance to wind-driven rain.
 |
Material: |
Extruded
Aluminum, Alloy 6063-T5
|
| Louver Depth: |
6” (152.4 mm)
|
| Blade: |
0.081”
(2.06 mm)
|
| Frame: |
0.081”
(2.06 mm)
|
| Test Standard: |
AMCA
Standard 500-L
|
| Water Penetration Test: |
Wind-Driven
Rain
|
| Free Area - 4 ft. x 4 ft.
unit: |
7.58 ft² (0.704 m²)
|
| Percent Free Area: |
47%
|
| Beginning Point of Water Penetration: |
1,250
fpm (6.35 m/s)
|
Air Volume Flow Rate at
Beginning Point of Water Penetration: |
9,475 cfm (4.47 m³/s)
|
Pressure Drop at
Beginning Point of Water Penetration: |
0.32
in. H2O (0.018 kPa)
|
| Wind-Driven Rain Water Penetration
Test: |
|
| Exterior
Wind Velocity: |
29
mph (13 m/s)
|
| Rainfall
Rate: |
3”
(75 mm)/hr
|
| Effectiveness: |
100%
|
| Core Ventilation: |
689 fpm (3.5 m/s)
|
| Exterior
Wind Velocity: |
50
mph (22 m/s)
|
| Rainfall
Rate: |
8”
(200 mm)/hr
|
| Effectiveness: |
99.1%
|
| Core Ventilation: |
295 fpm (1.5 m/s)
|
Product Submittal (PDF);
Specification Document (PDF);
AutoCAD Drawing (PDF)
(DWG)
SCH7 is a Storm Class combination louver designed and rated
to provide high volume intake and exhaust ventilation and the greatest level
of protection against water penetration. The design incorporates exterior and
interior louver modules that afford the designer optimum flexibility in aesthetic,
economic and performance considerations.
 |
Material: |
Extruded
Aluminum, Alloy 6063-T5
|
| Louver Depth: |
7”
(177.8 mm)
|
| Front Blade: |
0.081”
(2.06 mm)
|
| Back Blade: |
0.063”
(1.60 mm)
|
| Frame: |
0.081”
(2.06 mm)
|
| Test Standard: |
AMCA
Standard 500-L
|
| Water Penetration Test: |
Wind-Driven
Rain
|
| Free Area - 4 ft. x 4 ft.
unit: |
8.07
ft² (0.75 m²)
|
| Percent Free Area: |
50%
|
| Beginning Point of Water Penetration: |
919
fpm (4.67 m/s)
|
Air Volume Flow Rate at
Beginning Point of Water Penetration: |
7,416
cfm (3.50 m³/s)
|
Pressure Drop at
Beginning Point of Water Penetration: |
0.028
in. H2O (0.007 kPa)
|
| Wind-Driven Rain Water Penetration
Test: |
|
| Exterior
Wind Velocity: |
29
mph (13 m/s)
|
| Rainfall
Rate: |
3”
(75 mm)/hr
|
| Effectiveness: |
99.6%
|
| Core Ventilation: |
295
fpm (1.5 m/s)
|
Product Submittal (PDF);
Specification Document (PDF);
AutoCAD Drawing (PDF)
(DWG)
SCH701 is a Storm Class louver designed and rated to provide high volume intake and exhaust ventilation and the greatest level of protection against water penetration. The design incorporates a drainable head member and horizontal blades to provide maximum resistance to wind-driven rain.
 |
Material: |
Extruded
Aluminum, Alloy 6063-T5
|
| Louver Depth: |
7” (177.8 mm)
|
| Blade: |
0.081”
(2.06 mm)
|
| Frame: |
0.081”
(2.06 mm)
|
| Test Standard: |
AMCA
Standard 500-L
|
| Water Penetration Test: |
Wind-Driven
Rain
|
| Free Area - 4 ft. x 4 ft.
unit: |
7.17 ft² (0.666 m²)
|
| Percent Free Area: |
45%
|
| Beginning Point of Water Penetration: |
1,250
fpm (6.35 m/s)
|
Air Volume Flow Rate at
Beginning Point of Water Penetration: |
8,962 cfm (4.22 m³/s)
|
Pressure Drop at
Beginning Point of Water Penetration: |
0.49 in. H2O (0.122 kPa)
|
| Wind-Driven Rain Water Penetration
Test: |
|
| Exterior
Wind Velocity: |
29
mph (13 m/s)
|
| Rainfall
Rate: |
3”
(75 mm)/hr
|
| Effectiveness: |
99.9%
|
| Core Ventilation: |
689 fpm (3.5 m/s)
|
| Exterior
Wind Velocity: |
50
mph (22 m/s)
|
| Rainfall
Rate: |
8”
(200 mm)/hr
|
| Effectiveness: |
99.1%
|
| Core Ventilation: |
394 fpm (2.0 m/s)
|
Product Submittal (PDF);
Specification Document (PDF);
AutoCAD Drawing (PDF)
(DWG)
SCH8 is a Storm Class combination louver designed and rated
to provide high volume intake and exhaust ventilation and the greatest level
of protection against water penetration. The design incorporates exterior and
interior louver modules that afford the designer optimum flexibility in aesthetic,
economic and performance considerations.
 |
Material: |
Extruded
Aluminum, Alloy 6063-T5
|
| Louver Depth: |
8”
(203.2 mm)
|
| Front Blade: |
0.063”
(1.60 mm)
|
| Back Blade: |
0.063”
(1.60 mm)
|
| Frame: |
0.081”
(2.06 mm)
|
| Test Standard: |
AMCA
Standard 500-L
|
| Water Penetration Test: |
Wind-Driven
Rain
|
| Free Area - 4 ft. x 4 ft.
unit: |
7.60
ft² (0.71 m²)
|
| Percent Free Area: |
47%
|
| Beginning Point of Water Penetration: |
1,250
fpm (6.35 m/s)
|
Air Volume Flow Rate at
Beginning Point of Water Penetration: |
9,500
cfm (4.48 m³/s)
|
Pressure Drop at
Beginning Point of Water Penetration: |
0.45
in. H2O (0.112 kPa)
|
| Wind-Driven Rain Water Penetration
Test: |
|
| Exterior
Wind Velocity: |
29
mph (13 m/s)
|
| Rainfall
Rate: |
3”
(75 mm)/hr
|
| Effectiveness: |
100.0%
|
| Core Ventilation: |
689
fpm (3.5 m/s)
|
| Exterior
Wind Velocity: |
50
mph (22 m/s)
|
| Rainfall
Rate: |
8”
(200 mm)/hr
|
| Effectiveness: |
99.0%
|
| Core Ventilation: |
689
fpm (3.5 m/s)
|
Product Submittal (PDF);
Specification Document (PDF);
AutoCAD Drawing (PDF)
(DWG)
SCV201 is a Storm Class louver designed and rated to provide
high volume intake and exhaust ventilation and the greatest level of protection
against water penetration. The design incorporates a drainable head member,
vertical blades and a sloped sill to provide maximum resistance to wind-driven
rain.
 |
Material: |
Extruded
Aluminum, Alloy 6063-T5
|
| Louver Depth: |
2”
(54.8 mm)
|
| Blade: |
0.063”
(1.60 mm)
|
| Frame: |
0.063”
(1.60 mm)
|
| Test Standard: |
AMCA
Standard 500-L
|
| Water Penetration Test: |
Wind-Driven
Rain
|
| Free Area - 4 ft. x 4 ft.
unit: |
5.71
ft² (0.53 m²)
|
| Percent Free Area: |
36%
|
| Beginning Point of Water Penetration: |
1,250
fpm (6.35 m/s)
|
Air Volume Flow Rate at
Beginning Point of Water Penetration: |
7,137
cfm (3.37 m³/s)
|
Pressure Drop at
Beginning Point of Water Penetration: |
0.37
in. H2O (0.092 kPa)
|
| Wind-Driven Rain Water Penetration
Test: |
|
| Exterior
Wind Velocity: |
29
mph (13 m/s)
|
| Rainfall
Rate: |
3”
(75 mm)/hr
|
| Effectiveness: |
100.0%
|
| Core Ventilation: |
680
fpm (3.5 m/s)
|
| Exterior
Wind Velocity: |
50
mph (22 m/s)
|
| Rainfall
Rate: |
8”
(200 mm)/hr
|
| Effectiveness: |
99.9%
|
| Core Ventilation: |
600
fpm (3.5 m/s)
|
Product Submittal (PDF);
Specification Document (PDF);
AutoCAD Drawing (PDF)
(DWG)
SCV401 is a Storm Class louver designed and rated to provide
high volume intake and exhaust ventilation and the greatest level of protection
against water penetration. The design incorporates a drainable head member and
horizontal blades to provide maximum resistance to wind-driven rain.
 |
Material: |
Extruded
Aluminum, Alloy 6063-T5 |
| Louver Depth: |
4”
(101.6 mm)
|
| Blade: |
0.081”
(2.06 mm)
|
| Frame: |
0.081”
(2.06 mm)
|
| Test Standard: |
AMCA
Standard 500-L
|
| Water Penetration Test: |
Wind-Driven
Rain
|
| Free Area - 4 ft. x 4 ft.
unit: |
6.72
ft² (0.625 m²)
|
| Percent Free Area: |
42%
|
| Beginning Point of Water Penetration: |
1,250
fpm (6.35 m/s)
|
Air Volume Flow Rate at
Beginning Point of Water Penetration: |
8,400
cfm (3.96 m³/s)
|
Pressure Drop at
Beginning Point of Water Penetration: |
0.296
in. H2O (0.070 kPa)
|
| Wind-Driven Rain Water Penetration
Test: |
|
| Exterior
Wind Velocity: |
29
mph (13 m/s)
|
| Rainfall
Rate: |
3”
(75 mm)/hr
|
| Effectiveness: |
100.0%
|
| Core Ventilation: |
295
fpm (1.5 m/s)
|
| Exterior
Wind Velocity: |
50
mph (22 m/s)
|
| Rainfall
Rate: |
8”
(200 mm)/hr
|
| Effectiveness: |
99.1%
|
| Core Ventilation: |
98
fpm (0.5 m/s)
|
Product Submittal (PDF);
Specification Document (PDF);
AutoCAD Drawing (PDF)
(DWG)
SCV6 is a Storm Class louver designed and rated to provide
high volume intake and exhaust ventilation and the greatest level of protection
against water penetration. The design incorporates a drainable head member and
vertical blades to provide maximum resistance to wind-driven rain.
 |
Material: |
Extruded
Aluminum, Alloy 6063-T5 |
| Louver Depth: |
6”
(152.4 mm)
|
| Blade: |
0.081”
(2.06 mm)
|
| Frame: |
0.081”
(2.06 mm)
|
| Test Standard: |
AMCA
Standard 500-L
|
| Water Penetration Test: |
Wind-Driven
Rain
|
| Free Area - 4 ft. x 4 ft.
unit: |
8.73
ft² (0.81 m²)
|
| Percent Free Area: |
55%
|
| Beginning Point of Water Penetration: |
1,250
fpm (6.35 m/s)
|
Air Volume Flow Rate at
Beginning Point of Water Penetration: |
10,912
cfm (5.15 m³/s)
|
Pressure Drop at
Beginning Point of Water Penetration: |
0.20
in. H2O (0.050 kPa)
|
| Wind-Driven Rain Water Penetration
Test: |
|
| Exterior
Wind Velocity: |
29
mph (13 m/s)
|
| Rainfall
Rate: |
3”
(75 mm)/hr
|
| Effectiveness: |
100.0%
|
| Core Ventilation: |
689
fpm (3.5 m/s)
|
| Exterior
Wind Velocity: |
50 mph (22 m/s)
|
| Rainfall
Rate: |
8”
(200 mm)/hr
|
| Effectiveness: |
100.0%
|
| Core Ventilation: |
689
fpm (3.5 m/s)
|
Product Submittal (PDF);
Specification Document (PDF);
AutoCAD Drawing (PDF)
(DWG)
SCV602 is a Storm Class louver designed and rated to provide high volume intake and exhaust ventilation and the greatest level of protection against water penetration. The design incorporates a drainable head member and vertical blades to provide maximum resistance to wind-driven rain.
 |
Material: |
Extruded
Aluminum, Alloy 6063-T5
|
| Louver Depth: |
6” (152.4 mm)
|
| Blade: |
0.081”
(2.06 mm)
|
| Frame: |
0.081”
(2.06 mm)
|
| Test Standard: |
AMCA
Standard 500-L
|
| Water Penetration Test: |
Wind-Driven
Rain
|
| Free Area - 4 ft. x 4 ft.
unit: |
5.88 ft² (0.55 m²)
|
| Percent Free Area: |
37%
|
| Beginning Point of Water Penetration: |
1,250
fpm (6.35 m/s)
|
Air Volume Flow Rate at
Beginning Point of Water Penetration: |
7,350 cfm (3.47 m³/s)
|
Pressure Drop at
Beginning Point of Water Penetration: |
0.12 in. H2O (0.030 kPa)
|
| Wind-Driven Rain Water Penetration
Test: |
|
| Exterior
Wind Velocity: |
29
mph (13 m/s)
|
| Rainfall
Rate: |
3”
(75 mm)/hr
|
| Effectiveness: |
99.4%
|
| Core Ventilation: |
693 fpm (3.5 m/s)
|
| Exterior
Wind Velocity: |
50
mph (22 m/s)
|
| Rainfall
Rate: |
8”
(200 mm)/hr
|
| Effectiveness: |
99.1%
|
| Core Ventilation: |
691 fpm (3.5 m/s)
|
Product Submittal (PDF);
Specification Document (PDF);
AutoCAD Drawing (PDF)
(DWG)
SCV801 is a Storm Class louver designed and rated to provide high volume intake and exhaust ventilation and the greatest level of protection against water penetration. The design incorporates a drainable head member and vertical blades to provide maximum resistance to wind-driven rain.
 |
Material: |
Extruded
Aluminum, Alloy 6063-T5
|
| Louver Depth: |
8”
(203.2 mm)
|
| Front Blade: |
0.063”
(1.60 mm)
|
| Back Blade: |
0.063”
(1.60 mm)
|
| Frame: |
0.081”
(2.06 mm)
|
| Test Standard: |
AMCA
Standard 500-L
|
| Water Penetration Test: |
Wind-Driven
Rain
|
| Free Area - 4 ft. x 4 ft.
unit: |
7.60
ft² (0.71 m²)
|
| Percent Free Area: |
47%
|
| Beginning Point of Water Penetration: |
1,250
fpm (6.35 m/s)
|
Air Volume Flow Rate at
Beginning Point of Water Penetration: |
6,312 cfm (2.98 m³/s)
|
Pressure Drop at
Beginning Point of Water Penetration: |
0.10 in. H2O (0.025 kPa)
|
| Wind-Driven Rain Water Penetration
Test: |
|
| Exterior
Wind Velocity: |
29
mph (13 m/s)
|
| Rainfall
Rate: |
3”
(75 mm)/hr
|
| Effectiveness: |
99.6%
|
| Core Ventilation: |
703
fpm (3.5 m/s)
|
| Exterior
Wind Velocity: |
50
mph (22 m/s)
|
| Rainfall
Rate: |
8”
(200 mm)/hr
|
| Effectiveness: |
99.7%
|
| Core Ventilation: |
692
fpm (3.5 m/s)
|
Product Submittal (PDF);
Specification Document (PDF);
AutoCAD Drawing (PDF)
(DWG)
Downloadable Airolite Literature:
All Products Brochure (Sweets)
Corporate Brochure

You will need the free Acrobat Reader to view and print PDF documents. Click here to download a copy.
|