K6746MD
Airolite louver type K6746MD is Florida Building Code Approved for use in the High Velocity Hurricane Zone and Miami-Dade Approved use for where the room behind the louver is not designed to drain water penetrating into the room will house non-water resistance or water proof equipment, components or supplies, unless selected with optional factory VCD-40 control damper.
Specifications
| General | |
| Beginning Point of Water Penetration | 1,250 fpm (6.35 m/s) |
| Louver Depth | 6” (152.4 mm) |
| Percent Free Area | 59% (4 ft. x 4 ft.) |
| Pressure Drop at Beginning Point of Water Penetration | 0.20 in. wg (0.05kPa) |
| Test Standard | AMCA Standard 500-L Water Penetration and Air Performance, AMCA 540 Test Method for Louvers Impacted by Wind Borne Debris (Basic Protection, Missile Level D and Enhanced Protection, Missile Level E with 0.125 in. frame and blade material thickness), AMCA 550 High Velocity Wind Driven Rain |
Resources
Options and Accessories
Submittals
Specifications
Catalogs
Instruction Manuals
Drawings
Other Product Information
Warranty
- K6746MD Channel Installation (IOM# 487077) December 2024
- K6746MD Channel Installation with VCD-40 Damper (IOM# 487078) December 2024
- K6746MD Flange/Sleeve Installation (IOM# 487079) December 2024
- K6746MD Flange/Sleeve Installation with VCD-40 Damper (IOM# 487080) December 2024
- Stationary Louver Instruction Manual
Assistance